AT-8510: ATVOLT 110: 110VDC lines
ATVOLT DC Surge Protector series have got plenty of uses for this kind of equipment thanks to the flexibility of their design and connectors. Each SPD protects a pair of wires. Several protection stages are internally coordinated. ATVOLT Series contains a wide range of voltages. They are mainly used for DC supply lines of tens of volts.
They are installed in series with the line and they are able to withstand continuously currents ranging up to several amperes without significant line losses or consumption
ALVOLT SPDs withstand lightning secondary effects and power switching surges. They react to voltage impulses in a few nanoseconds, thus achieving a very low residual voltage, protecting even highly sensitive equipment.
Tested and certified as Type 3 according to regulations EN 61643-11 and GUIDE-BT-23 from REBT. Suitable for Categories I, II, III and IV equipment according to ITC-BT-23 from REBT.
They are installed in series with the line and they are able to withstand continuously currents ranging up to several amperes without significant line losses or consumption
ALVOLT SPDs withstand lightning secondary effects and power switching surges. They react to voltage impulses in a few nanoseconds, thus achieving a very low residual voltage, protecting even highly sensitive equipment.
Tested and certified as Type 3 according to regulations EN 61643-11 and GUIDE-BT-23 from REBT. Suitable for Categories I, II, III and IV equipment according to ITC-BT-23 from REBT.
- Recommended protection in both common and differential mode.
- Pluggable modules for its easier substitution in case of failure without the need of disconnecting the wiring. When substituting the module the line suffers no interruptions.
- It has a radiofrequency receptor in order to do the maintenance only with issuer equipment. When the RF SPD Tester is applied and the protector is working, the LED flickers green. If the cartridge is damage the LED does not flick.
- Earthing implemented through a metallic sheet opposite to the fixing DIN rail.
- Wide variety of SPDs for different working voltages.
- It remains inactive in normal conditions, without affecting the normal working of the line and without leakage.
- Low residual voltage for all working voltages.
- Very fast response.
- Mechanic connection for conductors through screws, which allows absorbing a highest amount of overvoltage ATVOLT SPDs have been tested in offi cial, independent laboratories, obtaining their characteristics according to relevant standards (related in the table)
Installation
ATVOLT Surge Protective Devices are to be installed in series with the DC supply line, cutting the cables and connecting the positive and negative terminals to the corresponding connectors. It is ery important to pay especial attention to these connections since a wrong connection can cause short- circuits at the equipment supply.
On another side, it is essential to connect orrectly the input and output terminals. Otherwise the SPD components will not work properly.
The lower terminal must be connected to the Earth Termination System, where the surge associated current must be derived. ATVOLT SPDs should be installed preferably as close to the equipment as possible.
The power should be disconnected during the installation of the SPD
On another side, it is essential to connect orrectly the input and output terminals. Otherwise the SPD components will not work properly.
The lower terminal must be connected to the Earth Termination System, where the surge associated current must be derived. ATVOLT SPDs should be installed preferably as close to the equipment as possible.
The power should be disconnected during the installation of the SPD
Các game casino-Casino có bịp không
Model / Reference | ATVOLT 110 AT-8510 |
Protection categories according to REBT: | I, II, III, IV |
Type of tests according to EN 61643-11: | Type 3 |
Nominal voltage: Un | 110VDC |
Maximum working voltage: Uc | 132VDC |
Maximum working current: Imax | 3A |
Nominal discharge current (wave 8/20μs): In | 5kA |
Combined wave tension: Uoc | 10kV |
Protection level (1,2/50μs wave): Up | 160V |
Protection level at In(8/20μs wave): Up(In) | 180V |
Response time: tr | <10ns |
Working temperature | -40oC đến +70oC |
SPD location | Indoor |
Type of connection | Series (two ports) |
Number of poles | 2 |
Dimensions | 13,5 x 90 x 80mm (0,75 mod. DIN43888) |
Fixing | DIN rail |
Enclosure material | Polyamide |
Insulation resistance | >1014Ω |
Autoextinguish enclosure: | Loại V-O theo UNE-EN60707 (UL94) |
Connections: | Maximum Section: 4mm² |
Certificated tests according to: IEC 61643-1, EN 61643-11 Complies with requirements of: UL 1449 Relevant standards: UNE 21186, NFC 17102, IEC 62305 |