Model: DAC1-13VG Series

Origin: CITEL / France

Download Catalogue: {关键字} (English)

Add to cart: {关键字}

The DAC1-13VG is an extreme duty Type 1+2+3 AC surge protector device designed to protect at the entrance of the electrical installation. This SPD is particularly useful in a high lightning density area where the risk of heavy surge current or even direct strike is high (eg: buildings equipped with lightning rods). The DAC1-13VG is one-pole SPD and can be used in common mode or common and differential mode. DAC1-13VG AC surge protectors are designed to be connected in multi-pole configuration to protect single-phase, 3-phase and 3-phase+Neutral AC networks, sometimes associated with a dedicated N/PE SPD.

  • Type 1 + 2 + 3 AC surge protector
  • VG Technology
  • In : 20 kA
  • Iimp : 12,5 kA on 10/350µs impulse
  • No leakage current
  • Pluggable module for each phase
  • Optimized to TOV
  • EN 61643-11, IEC 61643-11 certified
  • UL1449 ed.4 compliance

{关键字}

Các game casino-Casino có bịp không

 Citel Model
DAC1-13VG-31-275 DAC1-13VG-31-320
SPD type
following IEC test
Type 1+2+3
Network 230/400 V 3-phase+N
AC system TT-TNS
Max. AC operating voltage L-N (Uc) 275 Vac 320 Vac
Temporary Over Voltage (TOV) Charasteristics - 5
sec. without disconnectio (UT)
335 Vac withstand
Temporary Over Voltage (TOV) Charasteristics - 120
mn without disconnection or with safety disconnection
(UT)
440 Vac withstand
Temporary Over Voltage N/PE (TOV HT)
Without disconnection or with safety disconnection
1200 V/300A/200 ms withstand
Residual Current
Leakage current to Ground (Ipe)
None
Follow current (If) None
Nominal discharge current
15 x 8/20 μs impulses (In )
 20 kA 
Max. discharge current
max. withstand @ 8/20 μs by pole (Imax)
50 kA
Total Maximal discharge current (Imaz Total)
max. total withstand @ 8/20 μs
100 kA
Impulse current by pole
max. withstand 10/350μs by pole (Iimp)
12.5 kA
Total lightning current
max. total withstand @ 10/350μs (Total)
50 kA
Withstand on Combinaison waveform IEC 61643-11
Class III test: 1.2/50μs - 8/20μs (Uoc)
6 kV
Specific energy by pole
max. withstand 10/350 μs (W/R)
40 kJ/ohm
Protection mode(s) L/N and N/PE
Protection level L/N (Up L/N)
@ In (8/20μs) (Up)
1.5 kV 1.5 kV
Protection level N/PE (Up N/PE)
@ In (8/20μs) (Up)
1.5 kV 1.5 kV
Residuel voltage at L/N 5 kA (Up-5kA)
@ 5 kA (8/20μs)
0.7 kV 0.9 kV
Protection level N/PE at 5 kA (Up 5kA)
@ 5 kA (8/20μs)
0.7 kV 0.9 kV
Admissible short-circuit current (Isccr) 50000 A
Mechanical Characteristics
Technology VG 
SPD configuration 1-pole 3-phase+N
Connection to Network by screw terminals: 2.5-25 mm²
Format Plug-in modular box
Mounting Symmetrical rail 35 mm (EN60715)
Housing material Thermoplastic UL94-V0
Operating temperature -40/+85 °C
Protection rating IP20  
Failsafe mode Disconnection from AC network
Disconnection indicator 1 mechanical indicator by pole - Red/Green
Spare module(s) MDAC1-13VG-275 + MDAC1-50G-xxx MDAC1-13VG-320 + MDAC1-50G-xxx
Remote signaling of disconnection option DAC1-13VGS-31-275:
output on
changeover contact
option DAC1-13VGS-31-320:
output on
changeover contact
Dimensions See diagram
Disconnector
Thermal disconnector Internal
Installation ground fault breaker Type 'S' or delayed
Fuses Fuses 125 A min. - 315 A max. - Fuses Type gG
Standards
Standards compliance IEC 61643-11 / EN 61643-11 / UL1449 4ed.
Certification IEC 61463-11 / EN 61643-11
Part Number 821730234 821730334 