The DAC1-13VG is an extreme duty Type 1+2+3 AC surge protector device designed to protect at the entrance of the electrical installation. This SPD is particularly useful in a high lightning density area where the risk of heavy surge current or even direct strike is high (eg: buildings equipped with lightning rods). The DAC1-13VG is one-pole SPD and can be used in common mode or common and differential mode. DAC1-13VG AC surge protectors are designed to be connected in multi-pole configuration to protect single-phase, 3-phase and 3-phase+Neutral AC networks, sometimes associated with a dedicated N/PE SPD.
- Type 1 + 2 + 3 AC surge protector
- VG Technology
- In : 20 kA
- Iimp : 12,5 kA on 10/350µs impulse
- No leakage current
- Pluggable module for each phase
- Optimized to TOV
- EN 61643-11, IEC 61643-11 certified
- UL1449 ed.4 compliance
Các game casino-Casino có bịp không
Citel Model |
DAC1-13VG-31-275 | DAC1-13VG-31-320 |
SPD type following IEC test |
Type 1+2+3 | |
Network | 230/400 V 3-phase+N | |
AC system | TT-TNS | |
Max. AC operating voltage L-N (Uc) | 275 Vac | 320 Vac |
Temporary Over Voltage (TOV) Charasteristics - 5 sec. without disconnectio (UT) |
335 Vac withstand | |
Temporary Over Voltage (TOV) Charasteristics - 120 mn without disconnection or with safety disconnection (UT) |
440 Vac withstand | |
Temporary Over Voltage N/PE (TOV HT) Without disconnection or with safety disconnection |
1200 V/300A/200 ms withstand | |
Residual Current Leakage current to Ground (Ipe) |
None | |
Follow current (If) | None | |
Nominal discharge current 15 x 8/20 μs impulses (In ) |
20 kA | |
Max. discharge current max. withstand @ 8/20 μs by pole (Imax) |
50 kA | |
Total Maximal discharge current (Imaz Total) max. total withstand @ 8/20 μs |
100 kA | |
Impulse current by pole max. withstand 10/350μs by pole (Iimp) |
12.5 kA | |
Total lightning current max. total withstand @ 10/350μs (Total) |
50 kA | |
Withstand on Combinaison waveform IEC 61643-11 Class III test: 1.2/50μs - 8/20μs (Uoc) |
6 kV | |
Specific energy by pole max. withstand 10/350 μs (W/R) |
40 kJ/ohm | |
Protection mode(s) | L/N and N/PE | |
Protection level L/N (Up L/N) @ In (8/20μs) (Up) |
1.5 kV | 1.5 kV |
Protection level N/PE (Up N/PE) @ In (8/20μs) (Up) |
1.5 kV | 1.5 kV |
Residuel voltage at L/N 5 kA (Up-5kA) @ 5 kA (8/20μs) |
0.7 kV | 0.9 kV |
Protection level N/PE at 5 kA (Up 5kA) @ 5 kA (8/20μs) |
0.7 kV | 0.9 kV |
Admissible short-circuit current (Isccr) | 50000 A | |
Mechanical Characteristics | ||
Technology | VG | |
SPD configuration 1-pole | 3-phase+N | |
Connection to Network | by screw terminals: 2.5-25 mm² | |
Format | Plug-in modular box | |
Mounting | Symmetrical rail 35 mm (EN60715) | |
Housing | material Thermoplastic UL94-V0 | |
Operating temperature | -40/+85 °C | |
Protection rating | IP20 | |
Failsafe mode | Disconnection from AC network | |
Disconnection indicator | 1 mechanical indicator by pole - Red/Green | |
Spare module(s) | MDAC1-13VG-275 + MDAC1-50G-xxx | MDAC1-13VG-320 + MDAC1-50G-xxx |
Remote signaling of disconnection | option DAC1-13VGS-31-275: output on changeover contact |
option DAC1-13VGS-31-320: output on changeover contact |
Dimensions | See diagram | |
Disconnector | ||
Thermal disconnector | Internal | |
Installation ground fault breaker | Type 'S' or delayed | |
Fuses Fuses | 125 A min. - 315 A max. - Fuses Type gG | |
Standards | ||
Standards compliance | IEC 61643-11 / EN 61643-11 / UL1449 4ed. | |
Certification | IEC 61463-11 / EN 61643-11 | |
Part Number | 821730234 | 821730334 |