CITEL DS230-48DC, Protection for 48V DC power line
The DS230-48DC surge protector is designed to protect equipment connected to a DC power supply (or AC) against lightning surges.
These devices are based on high energy varistors (MOV) matched with the DC operating voltage (from 12 to 350 Vdc). The MOV are equipped with internal thermal disconnectors in order to provide safe end of life.
The indication of the disconnection status is provided by a mechanical indicator and is transmitted through a remote signal mechanism. The pluggable module allows an easy and fast maintenance.
The DS2x0-xxDC is DIN rail compatible and is connected in parallel on the DC line to be protected.
Characteristics DS230-48DC
MODEL |
DS230-48DC
|
SPD type following IEC test | 2 |
Network | DC or PV network 48Vdc |
Nominal DC voltage (Un-dc) | 48 Vdc |
Nominal PV voltage (Uocstc) | 48 Vdc |
Max. AC operating voltage L-N (Uc) | 50 Vac |
Max. PV operating voltage (Ucpv) | 65 Vdc |
Max. DC operating voltage (Uc) | 65 Vdc |
Max. load current (IL) | 20 A |
Residual Current (Ipe) Leakage current to Ground |
<0.1mA |
Operating current (Ic) Continious current at Uc |
<0.1mA |
PV Permanent Operating current (Icpv) Current consumption at Ucpv |
<0.1mA |
Follow current (If) | none |
Nominal discharge current (In) 15 x 8/20 µs impulses |
15 kA |
Max. discharge current (Imax) max. withstand @ 8/20 µs by pole |
30 kA |
Total Maximal discharge current (Imax Total) max. total withstand @ 8/20 µs |
60 kA |
Current withstand short circuit PV (Iscpv) |
1000 A |
Connection mode | +/-/PE |
Protection mode(s) | Common mode |
Protection level Up @ In (8/20μs) |
300 V |
Protection level L/PE (Up L/PE) @ In (8/20μs) |
300 V |
Residual Voltage at 3 kA (Up-3kA) @ 8/20μs |
230 V |
Mechanical characteristics | |
Technology | MOV |
SPD configuration | 2 poles |
Connection to Network | By screw terminals: 1.5-10mm² (actives wires) and 2.5-25mm² (ground) |
Format | Plug-in modular box |
Mounting | Symmetrical rail 35 mm (EN60715) |
Housing material | Thermoplastic UL94-V0 |
Operating temperature | -40/+85°C |
Protection rating | IP20 |
Failsafe behavior | disconnection from DC line |
Disconnection indicator | 2 mechanical indicator |
Spare module(s) | DSM230-48DC |
Remote signaling of disconnection | Option DS230S-48DC : output on changeover contact |
Dimensions | See diagram |
Disconnectors | |
Thermal disconnector | Internal |
Fuses | Fuses type gG - 50 A |
Standards | |
Standards compliance | IEC 61643-11 / EN 61643-11 / UL1449 4ed. |
Certification | UL |
Part Number | 390401 |