Tiếng Việt|English
Hotline: +84 89 88 99 578
{关键字}
{关键字}

Các game casino-Casino có bịp không

Model: DS254E-300/G

Origin: CITEL / France

Download Catalogue: {关键字} (Tiếng Việt) {关键字} (English)

Add to cart: {关键字}

CITEL DS254E Series AC power Surge Protective Devices (SPD) are designed to meet all your surge protection needs for any low voltage installation. DS254E are to install parallel with with the low voltage supply line three phase lines 230/400Vac (3L/N).

  • Type 1 + 2 unipolar surge protector
  • Iimp total: 100 kA on 10/350µs impulse
  • Imax : 140 kA on 8/20µs impulse
  • Internal disconnections, status indicators
  • Remote signaling
  • IEC 61643-11, EN 61643-11 and UL1449 ed.4 compliance

Các game casino-Casino có bịp không

Model DS254E-300 DS254E-300/G DS254E-400
SPD type following IEC test 1+2 1+2 1+2
Network 230/400 Vac 230/400 Vac 230/400 Vac
AC system TNS TT-TNS IT
Nominal line voltage (Un) 230/400 Vac 230/400 Vac 230/400 Vac
Max. PV operating voltage L-N (Uc) 330 Vac 330 Vac 440 Vac
Max. load current (IL) 100 A 100 A 100 A
Temporary Over Voltage (TOV) Charasteristics-5
sec.without disconnection
335 Vac withstand 335 Vac withstand 580 Vac withstand
Temporary Over Voltage (TOV) Charasteristics - 120
mn without disconnection or with safety disconnection
440 Vac disconnection 440 Vac disconnection 770 Vac disconnection
Temporary Over Voltage N/PE (TOV HT) (UT)
without disconnection or with safety disconnection
- 1200 V/300A/200 ms  withstand -
Residual Current (Ipe)
Leakage current to Ground
< 8 mA none < 8 mA
Operating current (Ic)
Continious current at Uc
2 mA 2 mA 2 mA
Follow current (If) None None None
Nominal discharge current (In)
15 x 8/20 μs impulses
70 kA 70 kA 70 kA
Max. discharge current (Imax)
max. withstand @ 8/20 μs by pole
140 kA 140 kA 140 kA
Impulse current by pole (limp)
max. withstand 10/350µs by pole
25 kA 25 kA 25 kA
Total lightning current  (ltotal)
max. total withstand @ 10/350μs 
100 kA 100 kA 100 kA
Admissible short-circuit current (lsccr) 50000 A 50000 A 50000 A
Connection mode(s) L/PE and N/PE L/N and N/PE L/PE and N/PE
Protection mode(s) Common Mode Common/ Differential Mode Common Mode
Protection level L/PE (Up L/PE)
@ In (8/20μs)
2.5 kV - 2.5 kV
Protection level L/N (Up L/N)
@ In (8/20μs)
- 2.5 kV -
rotection level N/PE (Up N/PE)
@ In (8/20μs)
2.5kV 1.5 kV 2.5 kV
Specific energy by pole
max. withstand 10/350 μs
156 kJ/ohm 156 kJ/ohm 156 kJ/ohm
Internal short circuit protection No No No
Internal Thermal protection Yes Yes Yes
Mechanical Characteristics
Technology MOV MOV + GDT MOV
SPD configuration 3-phase+Neutral
Connection to Network  By screw terminals: 6-35mm²/ by bus
Format 1-pole modular box assembled
Mounting ) Symmetrical rail 35 mm (EN60715
Housing material  Thermoplastic UL94-V0
Operating temperature -40 / +85 °C
Protection rating IP20
Failsafe behavior Disconnection
Disconnection indicator 3 mechanical indicator
Remote signaling of disconnection Output on changeover contact
Dimensions See diagram
Disconnectors
Thermal disconnector Internal
Installation ground fault breaker Type 'S' or delayed
Fuses Fuses type gG - 315 A
Standards
Standards compliance IEC 61643-11 / EN 61643-11 / UL1449 4ed.
Certification EAC
Part Number 3371 3411 3432
Type 1 AC Surge Protectors
Surge Protection for BTS

{关键字}

Surge Protection - Industrial sites

{关键字}

SPD Installation and Rules

{关键字}

Choosing Surge Protectors

{关键字}

Partners
  • {关键字}
  • {关键字}
  • {关键字}
  • {关键字}
  • {关键字}
Các game casino-Casino có bịp không