Model: DUT250VG

Origin: CITEL / France

Download Catalogue: {关键字} (English)

Add to cart: {关键字}

Các game casino-Casino có bịp không

The DUT250VG-300/G is a Compact and Heavy Duty Type 1 AC Surge Protector Device (SPD) designed to be connected at the entrance of the electrical installation, on a 3-Phase 230/400V AC network.

This SPD provides an efficient protection against direct and indirect effects and is particularly useful in a high lightning density area where the risk of heavy surge current or even direct strike is high (e.g.: buildings equipped with lightning rods or metallic poles, as radio base stations).

The DUT250VG-300/G is a 3-Phase+Neutral SPD and provides a common (L/G) and differential (L/N) mode protection. It complies to the Connection Type 2 configuration following IEC 62022-10-124.

This SPD is designed to withstand 25 kA lightning surge current (10/350 μs impulse) by pole. It is based on specific heavy duty GDTs and high energy MOV blocks : this technology allows the best behaviour possible on AC network (no follow current and no leakage current) and a very low residual voltage.

This SPD is built in a compact enclosure for DIN rail mounting.

{关键字}

Các game casino-Casino có bịp không

Model DUT250VG-300/G DUT250VG-300/TNS
SPD type following IEC test 1+2+3 1+2+3
Network 230/400 V 3-phase+N 230/400 V 3-phase+N
AC system TT-TNS TNS
Nominal line voltage (Un) 230/400 Vac 230/400 Vac
Max. PV operating voltage L-N (Uc) 255 Vac 255 Vac
Temporary Over Voltage (TOV) Charasteristics-5
sec.without disconnection
335 Vac withstand 335 Vac withstand
Temporary Over Voltage (TOV) Charasteristics - 120
mn without disconnection or with safety disconnection
440 Vac withstand 440 Vac withstand
Temporary Over Voltage N/PE (TOV HT)
without disconnection or with safety disconnection
1200 V/300A/200 ms withstand -
Residual Current (Ipe)
Leakage current to Ground
none none
Operating current (Ic)
Continious current at Uc
- none
Follow current (If) None none
Nominal discharge current (In)
15 x 8/20 μs impulses
40 kA 40 kA
Max. discharge current (Imax)
max. withstand @ 8/20 μs by pole
100 kA 100 kA
Impulse current by pole (limp)
max. withstand 10/350µs by pole
25 kA 25 kA
Total lightning current (Itotal)
max. total withstand @ 10/350μs
50 kA 50 kA
Withstand on Combinaison waveform IEC 61643-11
Class III test: 1.2/50μs - 8/20μs (Uoc)
6 kV 6 kV
Withstand on overvoltages IEEE C62.41.1 20 kV 20 kV
Admissible short-circuit current (lsccr) 50000 A 50000 A
Connection mode(s) L/N and N/PE L/N and L/PE
Protection mode(s) Common/Differential mode Common/Differential mode
Residual voltage (Up-in)
@ In (8/20 μs)
1.1 kV 1.1 kV
Protection level L/N (Up L/N)
@ In (8/20μs)
1.5 kV 1.5 kV
Protection level N/PE (Up N/PE)
@ In (8/20μs)
1.5 kV 1.5 kV
Specific energy by pole
max. withstand 10/350 μs
156 kJ/ohm 156 kJ/ohm
Mechanical Characteristics
Technology VG
SPD configuration 3- phase+Neutral
Connection to Network  By screw terminals: 6-35mm²/ by bus
Format Multipolar modular box
Mounting ) Symmetrical rail 35 mm (EN60715)
Housing material  Thermoplastic UL94-V0
Operating temperature -40 / +85 °C
Protection rating IP20
Failsafe behavior Disconnection
Disconnection indicator 3 mechanical indicator
Remote signaling of disconnection output on changeover contact
Dimensions See diagram
Disconnectors
Thermal disconnector Internal 
Installation ground fault breaker Type 'S' or delayed 
Fuses Fuses type gG - 315 A 
Standards
Standards compliance IEC 61643-11 / EN 61643-11 / UL1449 4ed. 
Certification EAC 
Part Number 3414  3597

 

 

Type 1 AC Surge Protectors