DAT CONTROLER® PLUS Early Streamer Emission Air Terminal.
DAT CONTROLER® REMOTE is an Early Streamer Emission (ESE) air terminal based on the electrical characteristics of lightning formation. The air terminal triggers the continuous upward leader before any other object within its radius of protection. DC Remote terminals offer the highest performance guarantees. Furthermore, they are provided with daily remote verification, with available data in real time at a web app using 2G/3G network. M2M communication and web portal for daily information on status of air terminals.
Các game casino-Casino có bịp không
Advance time (ΔT): obtained according to the tests described in the standards NF C 17102 and UNE21186.
- AENOR product certification.
- Daily remote verification, with avaliable data in real time at a web app using 2G/3G network.
- Withstand current 20 x 200kA + 5 x 250kA (10/350μs wave).
- Certificate of performance under rain (Insulation > 95% according to EN 60060).
- No external power supply required.
- Protection radius up to 20-107 meters according to NF C 17102 and UNE21186.
- Web portal for daily information on status of air terminals.
- M2M communication.
Certifications and tests
- AENOR Product Certification Nr. 058/000005 in accordance with UNE 21186 standard.
- Withstand current certificate for 20 impacts of 100 kA, 10/350 μs wave (ITE).
- Tested current:20 x 200kA + 5 x 250kA (10/350μs wave).
- Certified advance time.
- Certificate of unalterable performance under rain applying the standard EN 60060-1:2012.
- Radius protection certificate and regulation compliance (NFC 17-102, UNE 21186).
- Certificate of compliance with the standards of Electromagnetic Compatibility (EMC).
- Certificate of conformity with radio equipment directive R&TTE.
- Certificate for use in explosive athmospheres (ATEX).
- Manufactured according to ISO 9001 and following ISO 14001 environmental management standard.
INSTALLATION
- ESE air terminal protection radius depends on its height related to the surface to be protected, its advance time ΔT and the protection level.
- The installation of DAT CONTROLER® REMOTE air terminals should follow the standards NF C 17-102:2011, UNE 21186:2011 and NP 4426:2013.
- The air terminal should be at least 2 meters higher than any object to be protected.
- For correct operation of the remote testing, orient towards maximum solar gain, avoid shadows and obstacles and check GSM signal.
Các game casino-Casino có bịp không
Technical Datasheet | Early Streamer Emission Air Terminal | |||
Reference | AT-2515 | AT-2530 | AT-2545 | AT-2560 |
Model | Dat Controler Remote | |||
15 | 30 | 45 | 60 | |
Origin | AT3W - Spain | |||
Apply | Lightning protection | |||
Technology | Early Streamer Emission (ESE) | |||
Certified advance time ΔT) | 30 µs | µs 30 µs | 45 µs | 60 µs |
Protection radius (h = 6m, Level IV) according to NFC 17102 and UNE21186 | 52 m | 72 m | 90 m | 107m |
Withstand current higher than 200kA (10/350μs wave) | Yes | |||
Withstand current certificate for 20 impacts of 100 kA (10/350 μs) | Yes | |||
Tested current(10/350μs wave) | 20 x 200kA + 5 x 250kA | |||
Certificate of performance under rain | Good (Insulation > 95% according to EN 60060-1:2012) | |||
Certificate of use in explosive atmospheres (ATEX) | Yes | |||
Power supply | No external power supply required | |||
Standard deviation ratio ESE/Simple rod | < 0,8 | |||
DIM (L x W x H) | 120 x 120 x 551 mm | |||
Weight | 5000 g | |||
Materials | AISI 316L stainless steel | |||
IP code | IP67 | |||
Working temperature | -25 to 88 ºC | |||
Internal insulation | Polyurethane resin | |||
Fixing | M20 male thread | |||
Type of air terminal | Electropulsator (emits impulses) | |||
Remote testing & autodiagnostic features | ||||
Remote testing & autodiagnostic | Yes, by REMOTE device | |||
Autodiagnostic cycle | Every 24h in real time | |||
Communication | M2M,using 2G/3G network | |||
Method that user accessing / receiving data | Wb, mobile phone, tablet, computer | |||
Standards | ||||
Manufactured according to standards | ISO 9001 and following ISO 14001 environmental management standard | |||
Certification Stamp | AENOR (the Spanish National standards Association) Product Certification of accordance with UNE 21186 standard |
|||
Certificate of use in explosive atmospheres (ATEX) | Yes | |||
Radiocommunications and telecommunications standards | 1995/CE R&TTE; EMC | |||
Lightning standards | Complies with UNE 21186:2011; NF C 17-102:2011; NP 4426:2013 |
Các game casino-Casino có bịp không
PROTECTION LEVEL | h (m) |
DAT CONTROLER® REMOTE | |||
UNE 21186 NP 4426 NFC 17102 UNC 1185 |
AT-2515 | AT-2530 | AT-2545 | AT-2560 | |
PROTECTION LEVEL I |
2 | 13 | 19 | 25 | 31 |
4 | 25 | 38 | 51 | 63 | |
6 | 32 | 48 | 63 | 79 | |
8 | 33 | 49 | 64 | 79 | |
10 | 34 | 49 | 64 | 79 | |
PROTECTION LEVEL II |
2 | 15 | 22 | 28 | 35 |
4 | 30 | 44 | 57 | 69 | |
6 | 38 | 55 | 71 | 87 | |
8 | 39 | 56 | 72 | 87 | |
10 | 40 | 57 | 72 | 88 | |
PROTECTION LEVEL III |
2 | 18 | 25 | 32 | 39 |
4 | 36 | 51 | 64 | 78 | |
6 | 46 | 64 | 81 | 97 | |
8 | 47 | 65 | 82 | 98 | |
10 | 49 | 66 | 83 | 99 | |
PROTECTION LEVEL IV |
2 | 20 | 28 | 36 | 43 |
4 | 41 | 57 | 72 | 85 | |
6 | 52 | 72 | 90 | 107 | |
8 | 54 | 73 | 91 | 108 | |
10 | 56 | 75 | 92 | 109 |