Tiếng Việt|English
Hotline: +84 89 88 99 578
{关键字}
{关键字}

Các game casino-Casino có bịp không

Model: M50-277Y

Origin: CITEL / US

Download Catalogue: {关键字} (English)

Add to cart: {关键字}

Các game casino-Casino có bịp không

  • In : 20 kA
  • Imax : 50 kA/100kA
  • No leakage current
  • Visual indicator and audible Alarm
  • 2 formats :side or back nipple
  • UL 1449 4ed. certification

Technical Datasheet MS50-277Y

Model M50-277Y
System voltage 277/480 Vac
AC System 4W+G Wye
Frequency 50-60 Hz
Residual current
Leakage current at MCOV (Ipe)
none
Maximum Operating Voltage (L- PE) MCOV        320 V
L-N 320 V
  N-PE 280 V
L-L 560 V
Follow current If (A) none
Nominal discharge current (In)
15 x 8/20 μs impulses
20 kA
Max. discharge current L-N (Imax)
max. withstand @ 8/20 μs
50 kA
Max. discharge current N-PE (Imax)
max. withstand @ 8/20 μs
100 kA
Total lightning current Itotal (8/20 μs)
max. total withstand @ 8/20 μs
100 kA
Total lightning current Itotal (10/350 μs)
max. total withstand @ 10/350 μs
15 kA
Voltage Protection Rating (L-PE) VPR      1300V
 L-N  1200V
  N-PE  1300V
L-L 2100V
Shipping Dimensions 8x3.75x4.25 (inch)
Shipping Weight 2.4 lbs
Maximum Recommanded fuse 200 A Class J
Visual disconnection indicator LED
Sound disconnection indicator Continuous Buzzer
Wiring type AWG 12 wires
Maximum altitude 6500 ft
Operating Temperature -40/+85 C°
Housing material Aluminum cast
Mounting type Side or back nipple (Version A or B)
Threaded (M22) - NTP 1/2 adaptor available
Environmental rating IP 66/ NEMA 6
Location Installation Indoor / outdoor
Part Number
for A version (side nipple) 751501
for B version (back nipple) 751511

 