MDS boxes surge protectors are devices for low voltage electrical installations 120/220/277/480V (Single or Three Phase). These kits are based on the use of modular surge protectors : The implementation of these kits require no additional devices, are equipped with standard surge protectors and the corresponding overcurrent protection fuses. Many configurations are available.
- UL Type 1 AC SPD, IEC Type 1 + 2
- Imax: 300kA
- Imp: 25kA
- In : 20kA
- Pluggable module for each mode
Data sheet MDS300
CITEL Part Number | MDS300 |
-220Y -240Y |
|
AC Network | 220 /380V 240 /415V |
UL MCOV Uc | 275Vac |
TOV Withstand Ut | 335Vac |
ln IEC/UL Nominal Discharge Current | 20kA (x 15 impulses 8/20μs) |
lmax Max. Surge Current | 300kA |
Max. Lightning Current limp | 25kA (x1 impulse 10/350μs) |
VPR UL Voltage Protection Rating | 900V |
Up Protection Level at In Up | 1300V |
UL Short-Circuit Current Rating SCCR | 200kAIC |
Follow Current lf | none |
Replacement Module Number | 571500 |
Sine Wave Tracking | Yes, up to 50dB (10KHz to 100MHz) |
AC System | IT, TT, TN, Single, Split Phase, Delta, Wye |
Thermal Disconnector | UL 60691 |
Overcurrent Protection | No external OCP required |
Dimensions | See Dimensions and Diagram |
Connection | by screw terminals, #4 AWG Max. |
Remote Signal Indicator | 250Vac/0.5A Max.; 30Vdc/3A Max. |
Mounting | Wallmount by screws (not supplied) |
Operating Temp | -50°C to +185°C |
Operating Altitude | 16,000 ft (5,000m) |
Relative Humidity | 5 to 95% non-condensing, up to 100% external |
Enclosure Material | 16ga Steel, Optional Stainless Steel or PC NEMA 4X |
Environmental Rating | NEMA Type 4, 12 / IEC 60329 IP66 |
Weight | MDS200E 25lbs, MDS200S 17lbs |
Standards Compliance | |
IEC 61643-1 - INTERNATIONAL | Class I & II |
EN 61643-11 - EUROPE | Class I & II |
NF EN 61643-11 - FRANCE | Class I & II |
UL1449 3rd Edition - USA | Type 1 |
UL1449 3rd Edition - CANADA | Type 2 |
UL1283 - USA Type 2 SPDs Only | Type 2 SPDs Only |
Class 9091 32, Class 9091 92 | Class 9091 32, Class 9091 92 |
Directive 2002/95/EC | Directive 2002/95/EC |